Burglar Alarm Systems: Using the Net and Grading Systems
QUESTION: Can the Internet be used for monitoring of alarm signals? If so does it have a UL listing yet?
ANSWER: The use of the Internet to monitor burglary and fire alarm signals has become
an important and timely issue. Underwriters Laboratories (UL) has had several
ad hoc meetings, called the Industry Advisory Council, on the subject of Internet
monitoring for burglar alarm signals. This also includes the use of a company's
own internal network (i.e. intranet). The technology is referred to as "Packet
Data Switching Networks."
To explain UL and NFPA's involvement, UL has sole jurisdiction of burglar alarm
signal standards. While NFPA 72 writes code for fire alarm signaling, UL uses
its standard UL 864, Control Units for Fire-Protective Signaling Systems, to
list fire alarm control panels, communications methods and central station equipment
designed to NFPA 72. (More on the fire alarm side later.) After setting some
basic guidelines, UL's Burglary Council directed UL to explore this technology
and, if possible, proactively set an appropriate standard.
Whether monitoring is done using a proprietary central station on a second party,
there is a drastic reduction in telephone line charges. This is especially true
when you consider using this technology for fire alarm monitoring, since NFPA
72 requires two telephone lines when using digital alarm communications transmitters
(DACT). The use of a company's intranet facility for alarm signaling is very
cost-effective, as opposed to a second phone line.For others, the use of broadband
facilities, such as DSL and cable modems, makes the use of an already existing
broadband facility very attractive and cost effective, even when this service
is procured only for fire alarm signaling.
During the Industry Advisory Council meetings, UL asked the industry, installing
companies, manufacturers and consultants, for help in establishing a standard
for intranet and Internet monitoring. The result was a UL bulletin setting the
minimum requirements.
On the fire alarm side, UL deferred to NFPA. The Technical Committee On Supervising
Station Fire Alarm Systems of NFPA 72 discussed this technology during the last
cycle and concluded that it could be used as a primary and sole communications
path for fire alarm signaling. This was allowed as a Technical Interim Amendment
for the 1999 issue and appears in the 2002 issue under Other Transmission Technologies.
While actually not named per se, changes to the code allows its use.
The NFPA committee needed to decide how to handle equipment used for network
signal routing and how to deal with the requirement for prioritization of fire
alarm signals over a network that does not prioritize any signals. The result
was a Formal Interpretation (FI) that all equipment in the signal path must
be listed or otherwise approved by a national testing laboratory "for the
purpose." Fire alarm equipment must, therefore, be listed for "fire
alarm use" and shared on-premises communications equipment must be listed
for "the requirements applicable to communications network equipment."
Additionally, a Tentative Interim Amendment (TIA) gave an exception to the prioritization
requirements if end-to-end signal delivery timing is less than 90 seconds.
Several companies have listed equipment for both burglary and fire alarm signaling
to meet these requirements. This technology allows for extremely fast signaling,
while maintaining levels of supervision conforming with UL's definition of "line
security" not possible with DACT and favorably comparing with very expensive
active multiplex systems and two way radio systems.
Grading Stupefaction
QUESTION: I have heard and read that many systems are "Grade AA." What does this mean?
ANSWER: Grade AA is an obsolete descriptor. Unfortunately, its use is still widespread
among industry insiders. It refers to installed burglar alarm systems using
a method of line security. Strictly speaking, it goes further than the transmission
path, to a certain set of elements of a system including the on-premises installation
level, the transmission path, the implementation of "opening and closing"
signals, the central station listing and the level of central station response
and maintenance. All this operated in a closed system called a Grade AA service
and was one of the classic central station services. There were also several
other levels of central station service. Grade AA was used mainly for jewelry
stores, financial institutions, sensitive military installations or wherever
else a high security requirement was required.
Some years ago, UL "unbundled" the whole process with its "modular
certificate." Each of the above elements are defined separately on the
certificate and a particular level of each element is determined separately,
usually by the covering insurance company or authority. Whether line security
and encryption are used can be recorded on the certification on check boxes.